Fire Safety
AOV & Smoke Ventilation Installation from Kent, across the South East
Automatic Opening Vents clear smoke from escape routes so occupants can leave safely. We install, test and maintain AOV and smoke ventilation systems in residential and commercial buildings.
AOV & Smoke Vents for commercial, public and residential buildings
Automatic opening vents and smoke control systems for stairwells and common areas. Lumina Fire & Security, Kent-based, provides aov & smoke vents work across the South East.
What is included
- AOV window and roof vent installation
- Smoke ventilation control panels
- Integration with fire alarm systems
- Testing, servicing and repairs
How AOVs keep common stairs and corridors clear of smoke
Automatic opening vents are windows, roof vents or shaft dampers that open when smoke is detected or a firefighter’s switch is operated. In a block of flats, the aim is to stop smoke that escapes from a flat filling the common corridor and stairwell, so residents can leave and firefighters can reach the fire floor. A typical system has smoke detectors in the common areas, a control panel, actuators on each vent and a firefighter’s override switch.
- Head-of-stair vents release smoke from the stairwell
- Corridor or lobby vents on each floor
- Control panel with standby battery supply
- Firefighter override switches at access level
Natural or mechanical smoke ventilation?
Natural systems rely on smoke rising and leaving through vents, either directly to outside or via a vertical shaft, with replacement air coming in lower down. Mechanical systems use fans to extract smoke, which can serve longer corridors or deeper plans where natural ventilation alone would not work. The right choice depends on the building layout and the fire strategy, and many buildings already have the type set by their original design.
- Natural shafts and openable vents for simpler layouts
- Mechanical extract fans for long or deep corridors
- Pressurisation systems that keep smoke out of the stair
- Equipment made to the relevant part of BS EN 12101
Testing and servicing smoke ventilation systems
Smoke ventilation sits idle for years, so moving parts, actuators and batteries need regular exercise. Building managers usually carry out simple operational checks on a weekly or monthly routine, and a competent engineer services the full system periodically, often once a year. Guidance in BS 9999 and the manufacturer’s instructions set out what to check, and results should be recorded alongside the rest of the building’s fire safety records.
- Vents opened and closed from the panel and override switch
- Actuators, chains and seals checked for wear
- Batteries and power supplies tested under load
- Links to the fire alarm checked so detection opens the vents
Where AOVs are found and who is responsible for them
Automatic opening vents are most common in the stairs and corridors of purpose-built and converted blocks of flats, and also appear in student housing, care homes, hotels, offices and buildings with atria or basements. Because they are part of the building’s fire safety measures, the responsible person under the Fire Safety Order, usually the freeholder, managing agent or landlord, must keep them maintained. In leasehold blocks the cost is normally recovered through the service charge, so clear service reports help managing agents show residents what has been done and why it was needed.
- Purpose-built and converted blocks of flats
- Student accommodation, care homes and hotels
- Basements and atria with smoke control
- Freeholders and managing agents responsible for upkeep
Common AOV faults and how they are repaired
Most AOV problems come from parts that rarely move and sit exposed to the weather. Chain and linear actuators seize or burn out, vents get painted shut or blocked by later building work, and standby batteries in the control panel lose capacity without anyone noticing. Detector faults and damaged wiring to override switches are also common, as are vents that open but do not close fully, letting rain in. Repairs are usually like-for-like actuator or battery replacements, followed by an open-and-close test from every trigger point so the whole system is proven, not just the new part.
- Seized, burnt-out or misaligned actuators
- Control panel batteries that no longer hold charge
- Vents painted shut, obstructed or letting in water
- Wiring faults to override switches and detectors
How the job works
- 1Locate every vent and triggerWe find each vent, actuator, detector and override switch, and confirm from drawings or the fire strategy what should open, and when, for each trigger.
- 2Open and close each vent from every controlVents are operated from the panel, the smoke detectors and the firefighter switches, checking they open fully, close securely and respond to any fire alarm link.
- 3Load test panels and batteriesPower supplies and standby batteries are tested under load, so the vents will still open on battery if the mains supply fails during a fire.
- 4Report and repair faulty componentsYou get a report covering every vent and component, with failed actuators, seals or batteries replaced once approved and the system retested afterwards.

AOV & Smoke Vents near you
Local pages with details for the areas we cover most, plus every county and city we work in.
Official guidance
- Fire Safety (England) Regulations 2022 (GOV.UK)
- Approved Document B: fire safety (GOV.UK)
- Workplace fire safety: your responsibilities (GOV.UK)
Last reviewed: November 2026
AOV & Smoke Vents: common questions
Why does the AOV in our stairwell keep opening on its own?
Unwanted openings usually come from a detector reacting to dust, steam or insects, a fault on the control panel, or a signal from a linked fire alarm. Weather seals and actuators that have worn can also leave vents partly open. We check the panel’s event history, the detectors and the interface to the alarm to find which one is triggering it, then fix the cause.
Can you repair an AOV system installed by another company?
In most cases, yes. Actuators, panels and detectors from the common manufacturers can be repaired or replaced like for like, and where a part is no longer available we suggest a compatible alternative. We test the whole system after the repair, not just the failed part, so you know the vents open as the fire strategy intends.
Do window restrictors or security grilles affect an AOV?
They can. A vent needs to open to its designed free area to remove enough smoke, so restrictors, blinds, grilles or items stored on the window sill can stop it working properly. We check for obstructions during servicing and will point out anything that has been added since installation and is limiting how far a vent opens.
Should the AOV be linked to the building’s fire alarm?
Many systems have their own smoke detectors in the common parts, while others are triggered by the main fire alarm. Which arrangement is right is set by the fire strategy for the building. Where they are linked, the interface needs testing at each service so a detection opens the correct vents and does not open others on the wrong floor.
Related services
Fire Risk Assessments
A written assessment of the fire risks in your building, with a clear, prioritised list of what to do about them.
Fire Alarm Installation
Conventional, addressable and wireless fire alarm systems designed around your building.
Fire Alarm Servicing
Scheduled maintenance visits and certification to keep your system reliable and compliant.
Get in touch
Talk to an engineer about your building.
Free, no-obligation surveys and quotes for commercial, public and residential properties. Call us or drop us an email and we will get straight back to you.